Guidelines for national indoor environmental quality requirements: Difference between revisions

From Ediaqi Wiki
No edit summary
No edit summary
 
(3 intermediate revisions by the same user not shown)
Line 11: Line 11:
* Conducting continuous measurement of main indoor environmental quality indicators shall be required from continuously occupied spaces;  
* Conducting continuous measurement of main indoor environmental quality indicators shall be required from continuously occupied spaces;  
* It is good to support regulatory requirements with technical guidelines for the design and operation.
* It is good to support regulatory requirements with technical guidelines for the design and operation.




''Source: "Proposed modifications and guidelines for implementation of Article 11a ‘Indoorenvironmental quality’ in EPBD draft". Common proposal by REHVA, Nordic Ventilation Group and EUROVENT. June 19, 2023''
''Source: "Proposed modifications and guidelines for implementation of Article 11a ‘Indoorenvironmental quality’ in EPBD draft". Common proposal by REHVA, Nordic Ventilation Group and EUROVENT. June 19, 2023''
 
[[Category:Recommendations and guidelines]]
Category: Recommendations and guidelines

Latest revision as of 08:50, 14 July 2023

Summary of key guidelines for national indoor environmental quality regulatory requirements:

  • Minimum requirements for indoor air quality, thermal comfort, lighting, and acoustic are to be set in the regulation for new buildings and major renovations;
  • Indoor air quality, ventilation and thermal comfort requirements can be specified separately for residential and non-residential buildings;
  • In non-residential occupied buildings, ventilation capacity must be 7 L/s per person plus 0.7 L/s per m2 floor area, or alternatively CO2 concentrations of 900-1200 ppm, depending on occupant density, must be fulfilled;
  • In residential buildings an average ventilation capacity of a whole residence shall be 0.42 L/s per m2 floor area and 7 L/s supply air per person which are recommended to be supported with room-based ventilation rate requirements;
  • Room temperature ranges in residential and non-residential buildings must be specified for heating and cooling seasons;
  • Establishing a requirement on the lower limit of relative humidity in cold climates and upper limit in southern humid climates can be considered;
  • Requirements shall be specified so that it is possible to assess the compliance based on monitoring, measurements or simulations, therefore it is important to specify acceptable deviations;
  • Application of measuring and control devices for the monitoring and regulation of indoor environmental quality shall be required at relevant unit level;
  • Conducting continuous measurement of main indoor environmental quality indicators shall be required from continuously occupied spaces;
  • It is good to support regulatory requirements with technical guidelines for the design and operation.


Source: "Proposed modifications and guidelines for implementation of Article 11a ‘Indoorenvironmental quality’ in EPBD draft". Common proposal by REHVA, Nordic Ventilation Group and EUROVENT. June 19, 2023